NSN 5925-00-147-0749
Overload Switch
Plastic case material, single pole, double throw switch contact arrangement, moderately rugged fragility factor, pole quantity: 2.
Manufacturer part number APL11RR596-4 for national stock number 5925001470749.
Datasheet
-
Product description
Circuit Breaker NSN 5925-00-147-0749.
-
MPN or Model
APL11RR596-4
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Unit Weight (Est.)
0.1 lb -
Thread Pitch Diameters
+0.1177 to 0.1214 inches -
Body Length
Between 2.480 inches and 2.500 inches -
Body Width
1.515 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
1.940 inches -
Center To Center Distance Between Terminals Parallel To Width
Between 0.735 inches and 0.765 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
Between 2.050 inches and 2.070 inches -
Switch Contact Arrangement
Single pole, double throw -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
Between 0.735 inches and 0.765 inches -
Fragility Factor
Moderately rugged -
Boss Height
0.150 inches -
Mounting Surface To Terminal End Distance
2.625 inches -
Pole Quantity
2 -
Arc Quenching Method
Magnetic blowout -
Mounting Facility Type And Quantity
4 threaded hole -
Storage Type
General purpose warehouse -
Special Handling Feature
Magnetic -
Thready Qty Per Inch (tpi)
32 -
Maximum Continuous Load Current Rating Per Pole
50.0 amperes dc first location -
Operating Voltage Type And Rating Per Pole In Volts
32.0 dc all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2000.0 dc all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Magnetic all locations -
Trip Release Characteristic
Time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
2 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At each pole -
External Actuator Linkage Arrangement
One and two linked -
Auxiliary Switch Function And Quantity
1 alarm -
Internal Trip Release Configuration
Series trip all locations -
Thread Size
0.138 inches -
Switch Location And Position Designation
Internal at each pole -
Trip Delay Time In Seconds Per Rated Continuous Current
0.100 at 200 pct all locations and 1.700 at 200 pct all locations -
Inclosure Protection Type For Which Designed
Corrosion resistant and moisture resistant and shockproof and vibrationproof and fungus resistant -
Switch Terminal Type
Pin -
Switch Current Rating And Type In Amps
10.0 ac and 10.0 dc -
Switch Voltage Rating And Type In Volts
250.0 ac and 65.0 dc -
Unpackaged Unit Weight
7.400 ounces -
Thread Series Designator
Unc -
Terminal Type And Quantity
4 threaded stud
More from these suppliers
- 5925-00-407-1556 MPN UPL11-1R0-1004-1Circuit Breaker
- 5925-01-004-9293 MPN 203-2-1-61-252-4-1-1Circuit Breaker
- 5925-01-024-9568 MPN APL-1-1-62-302-MCircuit Breaker
- 5925-01-095-9989 MPN APGN-666-6AMP-60HZCircuit Breaker
- 5925-01-108-8047 MPN APL-111-6588-7Circuit Breaker
- 5925-01-157-9949 MPN UPG7-7332-1Circuit Breaker
- 5925-01-158-4512 MPN APGN-11-1-53-502Circuit Breaker
- 5925-01-165-2915 MPN 203-2-2-66-302-4-1-1ACircuit Breaker
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
![Mechanic Bill explains Overload Switch](/public/images/billy-thinking.png)
Pricing and Availability
Get a quote for 5925-00-147-0749 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
APL11RR596-4 | Sensata Technologies Maryland, Inc |
5-644-004 | Spx Corporation |
0005-644-004 | Spx Corporation |
Stock Check
![](/public/images/partscage_shelf3.png)