NSN 5925-00-164-2071
Overload Switch
Multipole-multiple actuator type body style, plastic case material, moderately rugged fragility factor, pole quantity: 2.
Manufacturer part number APL11-1-62-203-M for national stock number 5925001642071.
Datasheet
-
Product description
Circuit Breaker NSN 5925-00-164-2071.
-
MPN or Model
APL11-1-62-203-M
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Unit Weight (Est.)
0.5 lb -
Thread Pitch Diameters
+0.1177/+0.1214 inches -
Body Style
Multipole-multiple actuator type -
Body Length
2.510 inches -
Body Width
Between 1.437 inches and 1.563 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
Between 1.660 inches and 1.960 inches -
Center To Center Distance Between Terminals Parallel To Width
Between 0.719 inches and 0.781 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
Between 2.046 inches and 2.078 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
Between 0.719 inches and 0.781 inches -
Fragility Factor
Moderately rugged -
Boss Height
Between 0.109 inches and 0.171 inches -
Mounting Surface To Terminal End Distance
2.553 inches -
Pole Quantity
2 -
Arc Quenching Method
Magnetic blowout -
Mounting Facility Type And Quantity
4 threaded hole -
Storage Type
General purpose warehouse -
Thready Qty Per Inch (tpi)
32 -
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac all locations -
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Magnetic all locations -
Trip Release Characteristic
Time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
2 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At each pole -
External Actuator Linkage Arrangement
One and two linked -
Internal Trip Release Configuration
Series trip all locations -
Thread Size
0.138 inches -
Trip Delay Time In Seconds Per Rated Continuous Current
2.200 at 200 pct all locations and 20.000 at 200 pct all locations -
Inclosure Protection Type For Which Designed
Shock resistant and vibration resistant -
Frequency In Hertz
60.0 all locations -
Test Data Document
81349-mil-c-55629 specification (includes engineering type bulletins, brochures, etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type data on certain environmental and performance requirements and test conditions that are shown as "typical", "average", "", etc.). -
Thread Series Designator
Unc -
Terminal Type And Quantity
4 threaded stud -
Specification Data
81349-mil-c-55629/3 government specification
More from these suppliers
- 5985-01-245-8522 MPN 5543164Waveguide Assembly
- 5935-01-643-2030 MPN 2865651-1Electrical Connector Assembly
- 5975-01-222-0543 MPN 223-100012Strain Relief Clamp
- 5905-00-082-7510 MPN 0687-3331Composition Fixed Resistor
- 5905-00-106-1274 MPN 0686-9115Composition Fixed Resistor
- 5905-00-111-4727 MPN 0683-2725Composition Fixed Resistor
- 5905-00-120-9154 MPN 0684-4711Composition Fixed Resistor
- 5905-00-193-4470 MPN 2100-1740Nonprecision Wire Wound Variable Resistor
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-00-164-2071 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
APL11-1-62-203-M | Sensata Technologies Maryland, Inc |
264-200001-009 | Compro Computer Services, Inc. |
67P4-109 | Ellis & Watts International, Llc |
823HMG3-20-27 | Eaton Corp |
AM33-20-125VAC60-4 | Eaton Corp |
AM2A3-20-2 | Eaton Corp |
210-220-101 | Wood Electric Operations Potter And |
W92X11-2-20 | Wood Electric Operations Potter And |
AM2A3A20+2 | Eaton Corp |
W92X11-2-20 | Potter And Brumfield Div Amf Canada |
M55629/3-101 | Military Specifications |
MIL-PRF-55629/3 | Military Specifications |
10047-704 | Cooper Crouse- Hinds, Llc |
270107 | California Instruments Corp |
47A530118P3 | Lockheed Martin Corporation |
918203-138 | Raytheon Company |
2101-2020 | Br Communications Inc |
SB01 | Nautel Limited |
000-8005-117 | Boeing Company, The |
APL11-55629-101 | Sensata Technologies Maryland, Inc |
W92X11-2-20 | Tyco Electronics Corporation |
3105-0035 | Hewlett-packard Company |
0N231290 | National Security Agency |
190-220-101 | Tyco Electronics Corporation |
81-44911-001 | Raytheon Company |
78-8015-0147-5 | Systec Inc |
190-220-101 | Wood Electric Operations Potter And |
AM33MG6-20-250VAC60C4 | Eaton Corp |
XAM33MG3-20-250AC4 | Eaton Corp |
Stock Check