Overload Switch
Multipole-single actuator type body style, plastic case material, 2 poles, maximum continuous load current rating per pole: 400.0 amperes ac all locations and 400.0 amperes dc all locations.
Manufacturer part number LAB2400V for national stock number 5925001650367.
Datasheet
-
Product description
Circuit Breaker NSN 5925-00-165-0367.
-
MPN or Model
LAB2400V
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Body Style
Multipole-single actuator type -
Body Length
10.750 inches -
Body Width
8.250 inches -
Body Height
4.062 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
9.531 inches -
Center To Center Distance Between Terminals Parallel To Width
2.750 inches -
Unthreaded Mounting Hole Diameter
0.312 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
9.531 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
2.750 inches -
Boss Height
0.250 inches -
Pole Quantity
2 -
Mounting Facility Type And Quantity
4 unthreaded hole -
Maximum Continuous Load Current Rating Per Pole
400.0 amperes ac all locations and 400.0 amperes dc all locations -
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations and 250.0 dc all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
25000.0 ac all locations and 10000.0 dc all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Thermal-magnetic all locations -
Trip Release Characteristic
Time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
1 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
Between pole one and two -
Trip Delay Time In Seconds Per Rated Continuous Current
95.000 at 200 pct all locations and 550.000 at 200 pct all locations -
Trip Release Ambient Tempurature Rating
50.0 degrees celsius all locations -
Frequency In Hertz
60.0 all locations -
Terminal Type And Quantity
4 compression
More from these suppliers
- 5930-00-436-2202 MPN OT2C2Push Button
- 5950-01-258-2024 MPN 5250C79G01Electrical Coil
- 5930-01-529-7322 MPN 00782113782065Rotary Switch
- 5950-01-167-8861 MPN 505C633G31Opn Coil
- 5925-00-202-0938 MPN 207B508H01Circuit Breake Yoke
- 5925-01-041-5385 MPN 70E-0014Circuit Breaker
- 5925-01-343-8745 MPN EHB3100V/80E6685Circuit Breaker
- 5925-01-437-3937 MPN 6649C92G11Circuit Breaker Subassembly
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-00-165-0367 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
LAB2400V | Eaton Corporation |