NSN 5925-00-223-0360
Overload Switch
Multipole-multiple actuator type body style, plastic case material, moderately rugged fragility factor, pole quantity: 2.
Manufacturer part number 2XAM1516MG3-10-250-2-50 for national stock number 5925002230360.
Datasheet
-
Product description
Circuit Breaker NSN 5925-00-223-0360.
-
MPN or Model
2XAM1516MG3-10-250-2-50
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Body Style
Multipole-multiple actuator type -
Body Length
Between 3.709 inches and 3.729 inches -
Body Width
Between 2.021 inches and 2.041 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
Between 3.053 inches and 3.073 inches -
Center To Center Distance Between Terminals Parallel To Width
Between 1.021 inches and 1.041 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
Between 2.740 inches and 2.760 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
Between 1.021 inches and 1.041 inches -
Fragility Factor
Moderately rugged -
Boss Height
Between 0.146 inches and 0.166 inches -
Mounting Surface To Terminal End Distance
3.239 inches -
Pole Quantity
2 -
Arc Quenching Method
Magnetic blowout -
Mounting Facility Type And Quantity
4 threaded hole -
Storage Type
General purpose warehouse -
Thready Qty Per Inch (tpi)
32 -
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac all locations -
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Magnetic-hydraulic all locations -
Trip Release Characteristic
Time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
2 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At each pole -
External Actuator Linkage Arrangement
One and two linked -
Internal Trip Release Configuration
Series trip all locations -
Thread Size
0.138 inches -
Trip Delay Time In Seconds Per Rated Continuous Current
4.000 at 200 pct all locations and 18.000 at 200 pct all locations -
Inclosure Protection Type For Which Designed
Dustproof and fungus proof -
Frequency In Hertz
60.0 all locations -
Thread Series Designator
Unc -
Terminal Type And Quantity
4 threaded stud
More from these suppliers
- 5925-00-240-3424 MPN 0411CSM6-6-5Circuit Breaker
- 5925-00-308-7144 MPN AM1-A3-A-35-2Circuit Breaker
- 5925-00-502-9270 MPN 7-575KMG3Circuit Breaker
- 5925-00-754-9191 MPN 64-964AMG4Circuit Breaker
- 5925-00-755-5078 MPN 53-119MG3-3-416VAC2-400HZCircuit Breaker
- 5925-00-834-0272 MPN AM12HKMG6-15-50C5Circuit Breaker
- 5925-00-895-3649 MPN SM3-0.2-115-1Circuit Breaker
- 5925-00-905-9797 MPN AM1516MG3-2.5-250-3-400Circuit Breaker
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-00-223-0360 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
2XAM1516MG3-10-250-2-50 | Eaton Corp |