1-321-802-5889

NSN 5925-00-244-4410

Overload Switch

About this product

Plastic case material, 1 poles, air arc quenching method, thready qty per inch (tpi): 32.

Manufacturer part number 9300-10A for national stock number 5925002444410.

Datasheet

  • Product description

    Circuit Breaker NSN 5925-00-244-4410.

  • MPN or Model

    9300-10A

  • Schedule B
    8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi)
  • NMF (National Motor Freight)
    061300 - Circuit Breaker/switch NOI
  • Overall Length
    2.063 inches
  • Overall Height
    2.875 inches
  • Overall Width
    0.750 inches
  • Case Material
    Plastic
  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
    1.813 inches
  • Pole Quantity
    1
  • Arc Quenching Method
    Air
  • Mounting Facility Type And Quantity
    2 threaded hole
  • Thready Qty Per Inch (tpi)
    32
  • Maximum Continuous Load Current Rating Per Pole
    10.0 amperes dc single location
  • Operating Voltage Type And Rating Per Pole In Volts
    30.0 dc single location
  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
    1500.0 dc single location
  • Circuit Protection Type
    Overcurrent single location
  • Trip Release Method
    Magnetic single location
  • Trip Release Characteristic
    Time delay single location
  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
    150.0 single location
  • Reset Method
    Manual
  • Main Contact Tripping Mechanism Type
    Trip free
  • Manual Actuator Type And Quantity
    1 toggle
  • Actuator Function
    Reset
  • Thread Size
    0.138 inches
  • Trip Delay Time In Seconds Per Rated Continuous Current
    1200.000 at 125 pct single location and 2.800 at 400 pct single location
  • Trip Release Ambient Tempurature Rating
    75.0 degrees celsius single location
  • Precious Material
    Silver
  • Thread Series Designator
    Unc
  • Terminal Type And Quantity
    2 screw
Circuit Breaker

A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.

Mechanic Bill explains Overload Switch

Pricing and Availability

Get a quote for 5925-00-244-4410 circuit breaker
Quantity:
Your Email:
Your Name:
Company Name:
Optional reference:
Phone:
NSN 5925002444410

We do not share, sell, or distribute your information to any third party.
Privacy | Terms

All major credit cards accepted as well as gov. p-cards
Manufacturer Part Numbers and Alternates
MPN manufacturer part number Registrant or Supplier
9300-10A Schneider Electric Usa, Inc.
Stock Check
Availability of this NSN has not been updated recently. Submit the pricing and availbility form above to receive an up to date quote.