NSN 5925-00-252-1551
Overload Switch
Multipole-multiple actuator type body style, plastic case material, 3 poles, thready qty per inch (tpi): 32.
Manufacturer part number 3XAM151660250-2-60 for national stock number 5925002521551.
Datasheet
-
Product description
Circuit Breaker NSN 5925-00-252-1551.
-
MPN or Model
3XAM151660250-2-60
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Unit Weight (Est.)
1 lb -
Body Style
Multipole-multiple actuator type -
Body Length
3.719 inches -
Body Width
3.052 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
3.063 inches -
Center To Center Distance Between Terminals Parallel To Width
1.031 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.750 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.031 inches -
Boss Height
0.156 inches -
Mounting Surface To Terminal End Distance
3.359 inches -
Pole Quantity
3 -
Mounting Facility Type And Quantity
6 threaded hole -
Thready Qty Per Inch (tpi)
32 -
Maximum Continuous Load Current Rating Per Pole
60.0 amperes ac all locations -
Operating Voltage Type And Rating Per Pole In Volts
125.0 ac all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2000.0 ac all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Magnetic-hydraulic all locations -
Trip Release Characteristic
Time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations -
Ultimate Trip Time Per Pole In Seconds
20.000 all locations and 70.000 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
3 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At each pole -
External Actuator Linkage Arrangement
One, two, and three linked -
Internal Trip Release Configuration
Series trip all locations -
Thread Size
0.138 inches -
Trip Delay Time In Seconds Per Rated Continuous Current
10.000 at 150 pct all locations and 40.000 at 150 pct all locations and 4.500 at 200 pct all locations and 18.000 at 200 pct all locations and 2.000 at 300 pct all locations and 6.000 at 300 pct all locations -
Inclosure Protection Type For Which Designed
Fungus resistant and moisture resistant and explosion resistant -
Frequency In Hertz
60.0 all locations -
Thread Series Designator
Unc -
Terminal Type And Quantity
6 threaded stud
More from these suppliers
- 5925-00-107-4234 MPN AM12HKMG6-3-50VDC5Circuit Breaker
- 5925-00-262-6087 MPN AM12-15-250-400-14Circuit Breaker
- 5925-00-615-8777 MPN SM3-1-115VAC400CY58Circuit Breaker
- 5925-00-806-7493 MPN 53-119MG3-3AMPCircuit Breaker
- 5925-00-926-8425 MPN AM333MG6-50-250-14-400Circuit Breaker
- 5925-01-013-9650 MPN CD313D760-240-3Circuit Breaker
- 5925-01-023-2478 MPN JA3S-A3-A-15-2Circuit Breaker
- 5925-01-034-7501 MPN HE3-A3-10-1Circuit Breaker
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
![Mechanic Bill explains Overload Switch](/public/images/billy-thinking.png)
Pricing and Availability
Get a quote for 5925-00-252-1551 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
3XAM151660250-2-60 | Eaton Corp |
3XAM1516MG3-60-125VAC60-2 | Eaton Corp |
Stock Check