NSN 5925-00-261-6528
Overload Switch
Multipole-single actuator type body style, plastic case material, 3 poles, maximum continuous load current rating per pole: 200.0 amperes ac all locations and 200.0 amperes dc all locations.
Manufacturer part number NLB10-200AMP for national stock number 5925002616528.
Datasheet
-
Product description
Circuit Breaker NSN 5925-00-261-6528.
-
MPN or Model
NLB10-200AMP
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Unit Weight (Est.)
4.3 lb -
Body Style
Multipole-single actuator type -
Body Length
5.000 inches -
Body Width
4.750 inches -
Body Height
4.625 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
3.625 inches -
Center To Center Distance Between Terminals Parallel To Width
1.687 inches -
Unthreaded Mounting Hole Diameter
0.250 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.500 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.500 inches -
Boss Height
0.312 inches -
Pole Quantity
3 -
Mounting Facility Type And Quantity
2 unthreaded hole -
Maximum Continuous Load Current Rating Per Pole
200.0 amperes ac all locations and 200.0 amperes dc all locations -
Operating Voltage Type And Rating Per Pole In Volts
125.0 ac all locations and 125.0 dc all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 ac all locations and 5000.0 dc all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Thermal-magnetic all locations -
Trip Release Characteristic
Instantaneous all locations and time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
1 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At pole two -
Trip Delay Time In Seconds Per Rated Continuous Current
10.000 at 200 pct all locations and 180.000 at 200 pct all locations -
Inclosure Protection Type For Which Designed
Fungus resistant -
Trip Release Ambient Tempurature Rating
50.0 degrees celsius all locations -
Frequency In Hertz
400.0 all locations -
Test Data Document
81349-mil-c-17588 specification (includes engineering type bulletins, brochures, etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type data on certain environmental and performance requirements and test conditions that are shown as "typical", "average", "", etc.). -
Terminal Type And Quantity
6 screw
More from these suppliers
- 5905-00-070-9333 MPN 745-0698-000Composition Fixed Resistor
- 5930-00-083-8504 MPN 269-2178-00Rotary Switch Section
- 5950-00-147-5301 MPN 678-0035-00Reactor
- 5905-00-151-4659 MPN 724-0639-590Film Fixed Resistor
- 5940-00-155-7223 MPN 367-5060-00Terminal Board
- 5930-00-173-3500 MPN 259-2840-040Rotary Switch
- 5905-00-191-7798 MPN 747-7586-00Inductive Wire Wound Fixed Resistor
- 5935-00-192-4789 MPN 360-1060-00Telephone Jack
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
![Mechanic Bill explains Overload Switch](/public/images/billy-thinking.png)
Pricing and Availability
Get a quote for 5925-00-261-6528 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
NLB10-200AMP | Military Specifications |
MILC17588 | Military Specifications |
TN231Y200 | General Electric Co |
260-4743-000 | Rockwell Collins, Inc. |
Stock Check