NSN 5925-00-323-9920
Overload Switch
Multipole-multiple actuator type body style, plastic case material, moderately rugged fragility factor, pole quantity: 2.
Manufacturer part number APL-11-1-42-153-M for national stock number 5925003239920.
Datasheet
-
Product description
Circuit Breaker NSN 5925-00-323-9920.
-
MPN or Model
APL-11-1-42-153-M
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Unit Weight (Est.)
0.4 lb -
Thread Pitch Diameters
+0.1177/+0.1214 inches -
Body Style
Multipole-multiple actuator type -
Body Length
2.510 inches -
Body Width
1.500 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
Between 1.660 inches and 1.960 inches -
Center To Center Distance Between Terminals Parallel To Width
0.750 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
Between 2.046 inches and 2.078 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches -
Fragility Factor
Moderately rugged -
Boss Height
0.140 inches -
Mounting Surface To Terminal End Distance
2.553 inches -
Pole Quantity
2 -
Arc Quenching Method
Magnetic blowout -
Mounting Facility Type And Quantity
4 threaded hole -
Storage Type
General purpose warehouse -
Special Handling Feature
Magnetic -
Thready Qty Per Inch (tpi)
32 -
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac all locations -
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Magnetic all locations -
Trip Release Characteristic
Time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
2 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At each pole -
External Actuator Linkage Arrangement
One and two linked -
Internal Trip Release Configuration
Series trip all locations -
Thread Size
0.138 inches -
Trip Delay Time In Seconds Per Rated Continuous Current
2.100 at 200 pct all locations and 20.000 at 200 pct all locations -
Inclosure Protection Type For Which Designed
Fungus resistant and moisture resistant and salt spray proof and shock resistant and vibration resistant -
Frequency In Hertz
400.0 all locations -
Test Data Document
81349-mil-c-55629 specification (includes engineering type bulletins, brochures, etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type data on certain environmental and performance requirements and test conditions that are shown as "typical", "average", "", etc.). -
Thread Series Designator
Unc -
Terminal Type And Quantity
4 threaded stud -
Specification Data
55629-mil-c-55629/3 government specification
More from these suppliers
- 5925-00-155-2587 MPN AM3A3A3A16Circuit Breaker
- 5925-00-164-2965 MPN AM1516MG3-15-28-Circuit Breaker
- 5925-00-185-4015 MPN AM12-15-120-5-60Circuit Breaker
- 5925-00-248-5734 MPN HB2Z2-109Circuit Breaker
- 5925-00-279-3479 MPN 3363SMG4-15-250-60-2Circuit Breaker
- 5925-00-407-7660 MPN HB2Z2-122Circuit Breaker
- 5925-00-465-8571 MPN 3363S2-2-2CURVE2Circuit Breaker
- 5925-00-542-8895 MPN AM13MG60-5-117VAC60C4Circuit Breaker
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-00-323-9920 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
APL-11-1-42-153-M | Sensata Technologies Maryland, Inc |
JA-2-C3-15 | Eaton Corp |
M55629/3-096 | Military Specifications |
MIL-C-55629/3 | Military Specifications |
APL-11-55269/3-096 | Sensata Technologies Maryland, Inc |