NSN 5925-00-502-5718
Overload Switch
Multipole-single actuator type body style, plastic case material, moderately rugged fragility factor, pole quantity: 2.
Manufacturer part number TE22050 for national stock number 5925005025718.
Datasheet
-
Product description
Circuit Breaker NSN 5925-00-502-5718.
-
MPN or Model
TE22050
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
Body Style
Multipole-single actuator type -
Body Length
6.310 inches -
Body Width
2.750 inches -
Body Height
3.567 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
5.250 inches -
Center To Center Distance Between Terminals Parallel To Width
1.375 inches -
Unthreaded Mounting Hole Diameter
0.190 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.880 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.375 inches -
Fragility Factor
Moderately rugged -
Boss Height
0.187 inches -
Pole Quantity
2 -
Arc Quenching Method
Air -
Mounting Facility Type And Quantity
4 unthreaded hole -
Storage Type
General purpose warehouse -
Cubic Measure
61.896 cubic inches -
Maximum Continuous Load Current Rating Per Pole
50.0 amperes ac all locations and 50.0 amperes dc all locations -
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations and 250.0 dc all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 ac all locations and 7500.0 dc all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Thermal-magnetic all locations -
Trip Release Characteristic
Instantaneous all locations and time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
1 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At pole two -
Trip Delay Time In Seconds Per Rated Continuous Current
360.000 at 200 pct all locations -
Inclosure Protection Type For Which Designed
General purpose -
Trip Release Ambient Tempurature Rating
40.0 degrees celsius all locations -
Frequency In Hertz
60.0 all locations -
Terminal Type And Quantity
4 compression
More from these suppliers
- 4920-00-072-8714 MPN 11C1940P1Aircraft Maintenance Fixture
- 4920-00-085-8031 MPN 519D677G1Flow Con Valve Assy
- 5905-00-097-0201 MPN K7101558Resistive Disc
- 5930-00-108-6804 MPN M7462441-1Toggle Switch
- 5950-00-198-5913 MPN M7467171Power Transformer
- 5950-00-392-0140 MPN 209A653PC6Electrical Coil
- 5945-00-399-0381 MPN CR2824TC121AF38Thermal Relay
- 4920-00-510-1560 MPN 1C2515Concen Test Fixture
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-00-502-5718 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
TE22050 | General Electric Co |