NSN 5925-00-557-4030
Overload Switch
Mtg holes 2 rows of 2 holes each spaced 1.375 in.Apart,rows spaced 4.844 in. Apart off center.
Manufacturer part number 1532-384 for national stock number 5925005574030.
Datasheet
-
Product description
Circuit Breaker NSN 5925-00-557-4030.
-
MPN or Model
1532-384
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
Overall Length
6.000 inches -
Overall Height
3.968 inches -
Overall Width
2.750 inches -
Case Material
Plastic -
Unthreaded Mounting Hole Diameter
0.188 inches -
Pole Quantity
2 -
Arc Quenching Method
Deion -
Mounting Facility Type And Quantity
4 unthreaded hole -
Maximum Continuous Load Current Rating Per Pole
30.0 amperes ac all locations and 30.0 amperes dc all locations -
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations and 125.0 dc all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
7500.0 ac all locations and 7500.0 dc all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Thermal-magnetic all locations -
Trip Release Characteristic
Instantaneous all locations and time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
1 toggle -
Trip Delay Time In Seconds Per Rated Continuous Current
100.000 at 200 pct all locations -
Trip Release Ambient Tempurature Rating
25.0 degrees celsius all locations -
Terminal Type And Quantity
4 screw
More from these suppliers
- 5930-00-254-0996 MPN T-7607866-4REV9Rotary Switch
- 5905-00-333-1125 MPN CVE55S9102-16507ITEM31Inductive Wire Wound Fixed Resistor
- 5905-00-333-1151 MPN S1115246Resistor
- 5950-00-338-9515 MPN S1397085Reactor
- 5930-00-375-6042 MPN 1JH7PC31BContact Segment
- 4820-00-388-6868 MPN D15-394CPC15Fluid Valve Stem
- 4820-00-388-6891 MPN D15-672P138Fluid Valve Stem
- 5950-00-587-7600 MPN X19ZG8Electrical Coil
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-00-557-4030 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
1532-384 | Westinghouse Electric Corp |
1532384 | Westinghouse Electric Corp |