NSN 5925-00-660-7589
Overload Switch
Plastic case material, moderately rugged fragility factor, 3 poles, arc quenching method: magnetic blowout.
Manufacturer part number P3363MG4-10 for national stock number 5925006607589.
Datasheet
-
Product description
Circuit Breaker NSN 5925-00-660-7589.
-
MPN or Model
P3363MG4-10
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
Body Length
Between 5.240 inches and 5.260 inches -
Body Width
Between 2.990 inches and 3.010 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
Between 4.349 inches and 4.369 inches -
Center To Center Distance Between Terminals Parallel To Width
Between 0.990 inches and 1.010 inches -
Unthreaded Mounting Hole Diameter
0.190 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
Between 4.349 inches and 4.369 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
Between 0.990 inches and 1.010 inches -
Fragility Factor
Moderately rugged -
Boss Height
Between 0.209 inches and 0.229 inches -
Mounting Surface To Terminal End Distance
Between 3.303 inches and 3.323 inches -
Pole Quantity
3 -
Arc Quenching Method
Magnetic blowout -
Mounting Facility Type And Quantity
4 unthreaded hole -
Storage Type
General purpose warehouse -
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac all locations and 10.0 amperes dc all locations -
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations and 120.0 dc all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations and 2000.0 dc all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Magnetic-hydraulic all locations -
Trip Release Characteristic
Instantaneous all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
1 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At pole two -
Internal Trip Release Configuration
Series trip all locations -
Inclosure Protection Type For Which Designed
Dustproof -
Frequency In Hertz
60.0 all locations -
Terminal Type And Quantity
6 threaded stud
More from these suppliers
- 5925-00-054-4152 MPN PAM12HKMG6-0-5-50VDCCircuit Breaker
- 5925-00-103-6378 MPN AM3-B3-A3-ACircuit Breaker
- 5925-00-112-3460 MPN 71-168-2MG6Circuit Breaker
- 5925-00-174-3340 MPN P2263SMG4-0-5-250VAC60Circuit Breaker
- 5925-00-258-5235 MPN 0411TSHXCircuit Breaker
- 5925-00-400-9024 MPN HE2-C3-2-250-400-1Circuit Breaker
- 5925-00-797-0860 MPN 006-10014Circuit Breaker Cover
- 5925-00-807-4305 MPN AM13MG3HK10-115VAC5Circuit Breaker
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-00-660-7589 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
P3363MG4-10 | Eaton Corp |