NSN 5925-00-706-9975
Overload Switch
Multipole-multiple actuator type body style, plastic case material, moderately rugged fragility factor, pole quantity: 3.
Manufacturer part number 3XAM17-25-208-54-400 for national stock number 5925007069975.
Datasheet
-
Product description
Circuit Breaker NSN 5925-00-706-9975.
-
MPN or Model
3XAM17-25-208-54-400
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Unit Weight (Est.)
1 lb -
Body Style
Multipole-multiple actuator type -
Bushing Length
Between 0.120 inches and 0.140 inches -
Body Length
Between 2.490 inches and 2.510 inches -
Body Width
Between 2.263 inches and 2.283 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
Between 1.180 inches and 1.200 inches -
Center To Center Distance Between Terminals Parallel To Width
Between 0.740 inches and 0.760 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
Between 1.802 inches and 1.822 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
Between 0.740 inches and 0.760 inches -
Fragility Factor
Moderately rugged -
Mounting Surface To Terminal End Distance
Between 1.990 inches and 2.010 inches -
Pole Quantity
3 -
Arc Quenching Method
Magnetic blowout -
Mounting Facility Type And Quantity
6 threaded hole -
Storage Type
General purpose warehouse -
Thready Qty Per Inch (tpi)
32 -
Maximum Continuous Load Current Rating Per Pole
25.0 amperes ac all locations -
Operating Voltage Type And Rating Per Pole In Volts
208.0 ac all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
3500.0 ac all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Magnetic-hydraulic all locations -
Trip Release Characteristic
Time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
3 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At each pole -
External Actuator Linkage Arrangement
One, two, and three linked -
Internal Trip Release Configuration
Series trip all locations -
Thread Size
0.138 inches -
Trip Delay Time In Seconds Per Rated Continuous Current
15.000 at 200 pct all locations and 45.000 at 200 pct all locations -
Inclosure Protection Type For Which Designed
Dustproof and fungus proof -
Frequency In Hertz
400.0 all locations -
Thread Series Designator
Unc -
Terminal Type And Quantity
6 tab w/screw
More from these suppliers
- 5935-00-578-9211 MPN DMS 79023BElectrical Receptacle Connector
- 5935-00-615-3637 MPN DMS 85040BElectrical Plug Connector
- 5935-01-091-5896 MPN B8-702-25Electrical Receptacle Connector
- 5935-01-219-6507 MPN DMS 87162BElectrical Receptacle Connector
- 5985-01-264-2764 MPN 558027Antenna Support
- 5935-01-286-3627 MPN L04028Electrical Receptacle Connector Body
- 5935-01-323-8583 MPN 86108-14Electrical Receptacle Connector Body
- 5930-01-330-8618 MPN L04372Rotary Switch
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
![Mechanic Bill explains Overload Switch](/public/images/billy-thinking.png)
Pricing and Availability
Get a quote for 5925-00-706-9975 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
3XAM17-25-208-54-400 | Eaton Corp |
3XAM17MG3-25-208AC54-400 | Eaton Corp |
DMS83059B | Dla Land And Maritime |
3XAM17-25-208-54-400 | Eaton Corp |
3XAM17MG3-25-208AC54-400 | Eaton Corp |
DMS83059B | Dla Land And Maritime |
Stock Check