NSN 5925-00-810-4898
Overload Switch
Single pole type body style, plastic case material, 2 poles, arc quenching method: air.
Manufacturer part number TE122040 for national stock number 5925008104898.
Datasheet
-
Product description
Circuit Breaker NSN 5925-00-810-4898.
-
MPN or Model
TE122040
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
Body Style
Single pole type -
Body Length
6.310 inches -
Body Width
2.750 inches -
Body Height
3.380 inches -
Case Material
Plastic -
Pole Quantity
2 -
Arc Quenching Method
Air -
Mounting Facility Type And Quantity
2 threaded hole -
Maximum Continuous Load Current Rating Per Pole
40.0 amperes ac all locations and 40.0 amperes dc all locations -
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations and 250.0 dc all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
7500.0 ac all locations and 7500.0 dc all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Thermal all locations -
Trip Release Characteristic
Instantaneous all locations and time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations -
Reset Method
Manual -
Trip Release Duty Cycle
Continuous all locations -
Trip Delay Time In Seconds Per Rated Continuous Current
92.000 at 150 pct all locations and 400.000 at 150 pct all locations and 30.000 at 200 pct all locations and 90.000 at 200 pct all locations -
Trip Release Ambient Tempurature Rating
25.0 degrees celsius all locations -
Terminal Type And Quantity
4 screw
More from these suppliers
- 5945-00-590-2508 MPN CR2810A14BL104Electromagnetic Relay
- 5950-00-898-0472 MPN 15D21-3Coil
- 5930-01-023-2564 MPN 104B2466P001Rotary Switch
- 5950-01-166-7622 MPN 55-501336662Electrical Coil
- 4920-00-070-7104 MPN 21C2207-021Stator Vane Assembly
- 5905-00-117-0057 MPN PL168D116REVAPC13Nonprecision Nonwire Wound Variable Resistor
- 5940-00-258-2270 MPN T4970059PC14Lug Terminal
- 5905-00-279-2777 MPN CR9033C4B55BCInductive Wire Wound Fixed Resistor
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-00-810-4898 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
TE122040 | General Electric Co |
TE122040 | General Electric Co |