NSN 5925-00-961-5268
Overload Switch
Multipole-single actuator type body style, plastic case material, moderately rugged fragility factor, pole quantity: 3.
Manufacturer part number EB3050V for national stock number 5925009615268.
Datasheet
-
Product description
Circuit Breaker NSN 5925-00-961-5268.
-
MPN or Model
EB3050V
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Unit Weight (Est.)
3.4 lb -
Body Style
Multipole-single actuator type -
Body Length
6.000 inches -
Body Width
4.125 inches -
Body Height
3.375 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
5.062 inches -
Center To Center Distance Between Terminals Parallel To Width
1.375 inches -
Unthreaded Mounting Hole Diameter
0.188 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.500 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.375 inches -
Fragility Factor
Moderately rugged -
Boss Height
0.125 inches -
Pole Quantity
3 -
Arc Quenching Method
Magnetic blowout -
Mounting Facility Type And Quantity
4 unthreaded hole -
Storage Type
General purpose warehouse -
Special Handling Feature
Magnetic -
Maximum Continuous Load Current Rating Per Pole
50.0 amperes ac all locations and 50.0 amperes dc all locations -
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations and 125.0 dc all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 ac all locations and 5000.0 dc all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Thermal-magnetic all locations -
Trip Release Characteristic
Time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
1 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At pole two -
Trip Delay Time In Seconds Per Rated Continuous Current
29.000 at 200 pct all locations and 120.000 at 200 pct all locations -
Inclosure Protection Type For Which Designed
Dustproof and general purpose -
Trip Release Ambient Tempurature Rating
50.0 degrees celsius all locations -
Frequency In Hertz
60.0 all locations -
Terminal Type And Quantity
6 compression
More from these suppliers
- 4820-00-289-1877 MPN 25J88PC222Safety Relief Valve
- 5945-00-603-5591 MPN H34Thermal Relay
- 5945-01-172-6356 MPN S456D817G01Relay
- 5925-00-492-2251 MPN S451D852G09Circuit Breaker
- 5925-00-608-0972 MPN S1764653Circuit Breaker Tripper
- 5925-00-826-1367 MPN 445D420SUB5Circuit Breaker
- 6110-00-959-3386 MPN 942C013G1S2Motor Controller
- 6105-00-222-4698 MPN 34J187ITEM1Motor Armature
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-00-961-5268 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
EB3050V | Westinghouse Electric Corp |
EA3050V | Westinghouse Electric Corp |