NSN 5925-01-142-0332
Overload Switch
Multipole-single actuator type body style, plastic case material, 3 poles, storage type: general purpose warehouse.
Manufacturer part number THED136060 for national stock number 5925011420332.
Datasheet
-
Product description
Circuit Breaker NSN 5925-01-142-0332.
-
MPN or Model
THED136060
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Unit Weight (Est.)
4.3 lb -
Body Style
Multipole-single actuator type -
Body Length
6.310 inches -
Body Width
4.125 inches -
Body Height
3.380 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
5.250 inches -
Center To Center Distance Between Terminals Parallel To Width
1.375 inches -
Unthreaded Mounting Hole Diameter
0.188 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.880 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.375 inches -
End Application
5895-01-077-6249 -
Boss Height
0.240 inches -
Pole Quantity
3 -
Mounting Facility Type And Quantity
4 unthreaded hole -
Storage Type
General purpose warehouse -
Special Handling Feature
Magnetic -
Maximum Continuous Load Current Rating Per Pole
60.0 amperes ac all locations -
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
18000.0 ac all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Thermal-magnetic all locations -
Trip Release Characteristic
Instantaneous all locations and time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
1 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At pole two -
Trip Delay Time In Seconds Per Rated Continuous Current
25.000 at 200 pct all locations and 140.000 at 200 pct all locations -
Trip Release Ambient Tempurature Rating
40.0 degrees celsius all locations -
Frequency In Hertz
60.0 all locations -
Terminal Type And Quantity
6 compression
More from these suppliers
- 5905-00-300-6316 MPN 647780G012Wire Wound Fixed Resistor
- 5930-00-399-0608 MPN 194B8435PC5Rotary Switch
- 5945-00-565-8436 MPN 218A4084P1Electromagnetic Relay
- 5945-01-223-9292 MPN CR2810-1553U3Electromagnetic Relay
- 5905-01-420-6196 MPN IC9033-E4D48Film Fixed Resistor
- 5905-00-456-0621 MPN 68A7100P202Nonprecision Wire Wound Variable Resistor
- 6110-01-116-3396 MPN 1C4482CTRA801BE3Magnetic Contactor
- 6110-01-218-2816 MPN 229B3503G1S2Motor Starter
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
![Mechanic Bill explains Overload Switch](/public/images/billy-thinking.png)
Pricing and Availability
Get a quote for 5925-01-142-0332 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
THED136060 | General Electric Co |
361X0647Q07BE5 | General Electric Co |
THD136060 | General Electric Co |
THED136060 | General Electric Co |
Stock Check