NSN 5925-01-193-0168
Overload Switch
Multipole-multiple actuator type body style, plastic case material, single pole, double throw switch contact arrangement, fragility factor: moderately rugged.
Manufacturer part number 5541996-1 for national stock number 5925011930168.
Datasheet
-
Product description
Circuit Breaker NSN 5925-01-193-0168.
-
MPN or Model
5541996-1
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Unit Weight (Est.)
2.5 lb -
Body Style
Multipole-multiple actuator type -
Body Length
Between 5.768 inches and 5.832 inches -
Body Width
Between 3.046 inches and 3.110 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
Between 3.480 inches and 3.614 inches -
Center To Center Distance Between Terminals Parallel To Width
Between 0.996 inches and 1.036 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
Between 3.515 inches and 3.579 inches -
Switch Contact Arrangement
Single pole, double throw -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
Between 0.996 inches and 1.056 inches -
Fragility Factor
Moderately rugged -
Boss Height
0.220 inches -
Mounting Surface To Terminal End Distance
Between 3.460 inches and 3.580 inches -
Pole Quantity
3 -
Arc Quenching Method
Magnetic blowout -
Mounting Facility Type And Quantity
6 threaded hole -
Storage Type
General purpose warehouse -
Thready Qty Per Inch (tpi)
32 -
Maximum Continuous Load Current Rating Per Pole
100.0 amperes ac all locations -
Operating Voltage Type And Rating Per Pole In Volts
480.0 ac all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
7500.0 ac all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Magnetic-hydraulic all locations -
Trip Release Characteristic
Time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
3 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At each pole -
External Actuator Linkage Arrangement
One, two, and three linked -
Auxiliary Switch Function And Quantity
1 alarm -
Internal Trip Release Configuration
Series trip all locations -
Thread Size
0.138 inches -
Switch Location And Position Designation
Internal at pole one -
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 at 200 pct all locations and 11.000 at 200 pct all locations -
Inclosure Protection Type For Which Designed
Fungus resistant -
Switch Terminal Type
Turret -
Switch Current Rating And Type In Amps
10.0 ac and 4.0 dc -
Switch Voltage Rating And Type In Volts
250.0 ac and 30.0 dc -
Frequency In Hertz
50.0 all locations or 60.0 all locations -
Unpackaged Unit Weight
2.000 pounds -
Thread Series Designator
Unc -
Terminal Type And Quantity
6 threaded stud
More from these suppliers
- 5905-00-160-6148 MPN 2696242PT385Film Fixed Resistor
- 4820-00-186-3820 MPN 810-1385722-31A22Globe Valve
- 4820-00-288-6804 MPN 6800H799347PCV5Globe Valve
- 4820-00-288-7836 MPN 571-3801-1302533PCV12Safety Relief Valve
- 1680-00-382-1723 MPN 989997Constant Speed Drive Governor
- 5930-00-458-4198 MPN 2919961-253Push-light Indicating Switch
- 1680-00-516-8137 MPN 62A129E1-1Aircraft Safety Belt
- 5935-00-853-7596 MPN 5013253Electrical Receptacle Connector
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-01-193-0168 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
5541996-1 | Naval Sea Systems Command |
CD3-A2A3A3-AB-100-480-2 | Eaton Corp |