NSN 5925-01-226-8319
Overload Switch
Multipole-multiple actuator type body style, plastic case material, single pole, double throw switch contact arrangement, fragility factor: moderately rugged.
Manufacturer part number MS55629/6-059 for national stock number 5925012268319.
Datasheet
-
Product description
Circuit Breaker NSN 5925-01-226-8319.
-
MPN or Model
MS55629/6-059
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Unit Weight (Est.)
0.5 lb -
Body Style
Multipole-multiple actuator type -
Body Length
2.510 inches -
Body Width
Between 2.156 inches and 2.344 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
Between 1.660 inches and 1.960 inches -
Center To Center Distance Between Terminals Parallel To Width
Between 0.719 inches and 0.781 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
Between 2.046 inches and 2.078 inches -
Switch Contact Arrangement
Single pole, double throw -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
Between 0.719 inches and 0.781 inches -
Fragility Factor
Moderately rugged -
Boss Height
Between 0.109 inches and 0.171 inches -
Mounting Surface To Terminal End Distance
2.800 inches -
Pole Quantity
3 -
Arc Quenching Method
Magnetic blowout -
Mounting Facility Type And Quantity
6 threaded hole -
Storage Type
General purpose warehouse -
Thready Qty Per Inch (tpi)
32 -
Maximum Continuous Load Current Rating Per Pole
7.0 amperes ac all locations -
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Magnetic all locations -
Trip Release Characteristic
Time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
3 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At each pole -
External Actuator Linkage Arrangement
One, two, and three linked -
Auxiliary Switch Function And Quantity
1 alarm -
Internal Trip Release Configuration
Series trip all locations -
Thread Size
0.138 inches -
Switch Location And Position Designation
Internal at pole one -
Trip Delay Time In Seconds Per Rated Continuous Current
2.200 at 200 pct all locations and 20.000 at 200 pct all locations -
Inclosure Protection Type For Which Designed
Fungus resistant and moisture resistant -
Switch Terminal Type
Tab, solder lug -
Switch Current Rating And Type In Amps
10.0 ac and 2.0 dc -
Switch Voltage Rating And Type In Volts
250.0 ac and 50.0 dc -
Frequency In Hertz
60.0 all locations -
Test Data Document
81349-mil-c-55629 specification (includes engineering type bulletins, brochures, etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type data on certain environmental and performance requirements and test conditions that are shown as "typical", "average", "", etc.). -
Thread Series Designator
Unc -
Terminal Type And Quantity
6 threaded stud -
Specification Data
81349-mil-c-55629/6 government specification
More from these suppliers
- 5905-00-001-2852 MPN MIL-R-10509/6Film Fixed Resistor
- 5905-00-001-7271 MPN MILR22097-3Nonprecision Nonwire Wound Variable Resistor
- 5905-00-004-7652 MPN RWR74S4R02FRInductive Wire Wound Fixed Resistor
- 5905-00-006-5496 MPN MILR55182-3Film Fixed Resistor
- 5905-00-006-6980 MPN RLR05C512JRFilm Fixed Resistor
- 5935-00-009-3015 MPN M83723/75R2212NElectrical Plug Connector
- 5935-00-020-7890 MPN MILC25955Electrical Receptacle Connector
- 5905-00-024-0590 MPN RER70F44R2RInductive Wire Wound Fixed Resistor
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-01-226-8319 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
MS55629/6-059 | Military Specifications |
M55629/6-059 | Military Specifications |
MIL-C-55629/6 | Military Specifications |