NSN 5925-01-233-3246
Overload Switch
Multipole-single actuator type body style, plastic case material, moderately rugged fragility factor, pole quantity: 3.
Manufacturer part number 6980ED8 PC 1 FIG 4 for national stock number 5925012333246.
Datasheet
-
Product description
Circuit Breaker NSN 5925-01-233-3246.
-
MPN or Model
6980ED8 PC 1 FIG 4
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Unit Weight (Est.)
8 lb -
Body Style
Multipole-single actuator type -
Body Length
6.500 inches -
Body Width
4.125 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
5.562 inches -
Center To Center Distance Between Terminals Parallel To Width
1.375 inches -
Unthreaded Mounting Hole Diameter
0.190 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
3.312 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.375 inches -
Fragility Factor
Moderately rugged -
Boss Height
0.187 inches -
Mounting Surface To Terminal End Distance
4.093 inches -
Pole Quantity
3 -
Arc Quenching Method
Deion -
Mounting Facility Type And Quantity
4 unthreaded hole -
Storage Type
General purpose warehouse -
Maximum Continuous Load Current Rating Per Pole
100.0 amperes ac and 100.0 amperes dc all locations -
Operating Voltage Type And Rating Per Pole In Volts
500.0 ac and 250.0 dc all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
15000.0 ac and 10000.0 dc all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Thermal-magnetic all locations -
Trip Release Characteristic
Instantaneous all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Nontrip free -
Manual Actuator Type And Quantity
1 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At pole two -
Inclosure Protection Type For Which Designed
General purpose -
Trip Release Ambient Tempurature Rating
50.0 degrees celsius all locations -
Frequency In Hertz
60.0 all locations -
Unpackaged Unit Weight
6.000 pounds -
Terminal Type And Quantity
2 threaded stud
More from these suppliers
- 5950-00-110-7805 MPN 42-2270Power Transformer
- 5930-00-410-1723 MPN 6984ED91-1Sensitive Switch
- 5950-00-446-5436 MPN 9-1989-20Electrical Coil
- 5950-00-773-2786 MPN 6999ED581 PIECE 1HElectrical Coil
- 5930-00-907-9446 MPN 86-346-9Element
- 5905-00-931-1470 MPN 57-1071-43Inductive Wire Wound Fixed Resistor
- 5930-01-035-5185 MPN E50KL200Switch Actuator Arm
- 5930-01-137-1356 MPN 6981ED173-6Push Switch
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-01-233-3246 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
6980ED8 PC 1 FIG 4 | Drs Power & Control Technologies, |
45-785 | Drs Power & Control Technologies, |
1279C57G02 | Eaton Corporation |