NSN 5925-01-249-7045
Overload Switch
Multipole-single actuator type body style, metal case material, single pole, double throw switch contact arrangement, fragility factor: moderately rugged.
Manufacturer part number M39019/04-335 for national stock number 5925012497045.
Datasheet
-
Product description
Circuit Breaker NSN 5925-01-249-7045.
-
MPN or Model
M39019/04-335
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Unit Weight (Est.)
0.3 lb -
Body Style
Multipole-single actuator type -
Bushing Length
0.380 inches -
Body Length
1.562 inches -
Body Width
1.281 inches -
Case Material
Metal -
Center To Center Distance Between Terminals Parallel To Length
0.906 inches -
Center To Center Distance Between Terminals Parallel To Width
0.625 inches -
Switch Contact Arrangement
Single pole, double throw -
Fragility Factor
Moderately rugged -
Mounting Surface To Terminal End Distance
1.828 inches -
Pole Quantity
2 -
Arc Quenching Method
Air -
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal -
Storage Type
General purpose warehouse -
Features Provided
High inrush protection -
Thready Qty Per Inch (tpi)
32 -
Maximum Continuous Load Current Rating Per Pole
12.5 amperes ac all locations and 12.5 amperes dc all locations -
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations and 50.0 dc all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac all locations and 500.0 dc all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Magnetic all locations -
Trip Release Characteristic
Time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
130.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
1 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At pole one -
Auxiliary Switch Function And Quantity
1 alarm -
Internal Trip Release Configuration
Series trip all locations -
Thread Size
0.375 inches -
Switch Location And Position Designation
Internal at pole one -
Trip Delay Time In Seconds Per Rated Continuous Current
0.500 at 200 pct all locations and 9.000 at 200 pct all locations -
Inclosure Protection Type For Which Designed
Fungus resistant -
Switch Terminal Type
Tab, solder lug -
Switch Current Rating And Type In Amps
0.5 ac and 0.5 dc -
Switch Voltage Rating And Type In Volts
120.0 ac and 50.0 dc -
Frequency In Hertz
60.0 all locations or 400.0 all locations -
Test Data Document
81349-mil-c-39019 specification (includes engineering type bulletins, brochures, etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type data on certain environmental and performance requirements and test conditions that are shown as "typical", "average", "", etc.). -
Thread Series Designator
Unef -
Terminal Type And Quantity
4 wire hook -
Specification Data
81349-mil-c-39019/4 government specification
More from these suppliers
- 5905-00-001-5675 MPN RV4LAYSA155CNonprecision Nonwire Wound Variable Resistor
- 5935-00-005-2843 MPN M83723/75R12128Electrical Plug Connector
- 5905-00-007-7188 MPN RLR05C680JPFilm Fixed Resistor
- 5905-00-008-6824 MPN RNC60C4992FRFilm Fixed Resistor
- 5905-00-009-3029 MPN RLR20C11R0GRFilm Fixed Resistor
- 5905-00-025-5987 MPN RNR60K2491FMFilm Fixed Resistor
- 5905-00-026-9156 MPN RN75G8062FFilm Fixed Resistor
- 5905-00-032-9522 MPN MILR55182-3Film Fixed Resistor
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-01-249-7045 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
M39019/04-335 | Military Specifications |
MIL-C-39019/4 | Military Specifications |