NSN 5925-01-294-5707
Overload Switch
Rectangular dimensional envelope body style, plastic case material, moderately rugged fragility factor, pole quantity: 2.
Manufacturer part number WC375/11-012 for national stock number 5925012945707.
Datasheet
-
Product description
Circuit Breaker NSN 5925-01-294-5707.
-
MPN or Model
WC375/11-012
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Unit Weight (Est.)
3 lb -
Body Style
Rectangular dimensional envelope -
Overall Length
6.312 inches -
Overall Height
2.750 inches -
Overall Width
4.156 inches -
Case Material
Plastic -
Unthreaded Mounting Hole Diameter
0.187 inches -
Fragility Factor
Moderately rugged -
Pole Quantity
2 -
Arc Quenching Method
Magnetic blowout -
Mounting Facility Type And Quantity
2 unthreaded hole -
Storage Type
General purpose warehouse -
Maximum Continuous Load Current Rating Per Pole
80.0 amperes ac all locations and 80.0 amperes dc all locations -
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations and 125.0 dc all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
7500.0 ac all locations and 5000.0 dc all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Thermal-magnetic all locations -
Trip Release Characteristic
Time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
1 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
Between pole one and two -
Trip Delay Time In Seconds Per Rated Continuous Current
100.000 at 200 pct all locations and 190.000 at 200 pct all locations -
Inclosure Protection Type For Which Designed
Fungus resistant -
Trip Release Ambient Tempurature Rating
40.0 degrees celsius all locations -
Frequency In Hertz
60.0 all locations -
Test Data Document
81348-w-c-375 specification (includes engineering type bulletins, brochures, etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type data on certain environmental and performance requirements and test conditions that are shown as "typical", "average", "", etc.). -
Terminal Type And Quantity
4 compression -
Specification Data
81348-w-c-375/11 government specification
More from these suppliers
- 5930-00-201-4504 MPN 7475Toggle Switch
- 5930-01-287-4300 MPN TH3222RBox Switch
- 5950-01-445-3219 MPN 75C149640P038Current Transformer
- 5905-01-660-7871 MPN YQD120N0025Thermal Resistor
- 5925-01-122-7144 MPN TEDXUVBRBUndervoltage Trip
- 5925-01-361-8836 MPN TFJ236200LL/TFKASA2AB1LSCircuit Breaker
- 5925-01-392-1769 MPN 139C4600G3Circuit Breaker Subassembly
- 6105-01-631-5039 MPN 929941Alternating Current Motor
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-01-294-5707 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
WC375/11-012 | Federal Specifications |
W-C-375/11 | Federal Specifications |
TEB122080 | General Electric Co |