NSN 5925-01-297-3995
Overload Switch
Plastic case material, single pole, double throw switch contact arrangement, moderately rugged fragility factor, pole quantity: 3.
Manufacturer part number G396183AG5R0A51 for national stock number 5925012973995.
Datasheet
-
Product description
Circuit Breaker NSN 5925-01-297-3995.
-
MPN or Model
G396183AG5R0A51
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Body Length
Between 2.490 inches and 2.510 inches -
Body Width
Between 2.490 inches and 2.510 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
Between 1.928 inches and 1.948 inches -
Center To Center Distance Between Terminals Parallel To Width
Between 0.745 inches and 0.755 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
Between 2.052 inches and 2.072 inches -
Switch Contact Arrangement
Single pole, double throw -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
Between 0.745 inches and 0.755 inches -
Fragility Factor
Moderately rugged -
Boss Height
Between 0.130 inches and 0.150 inches -
Mounting Surface To Terminal End Distance
Between 2.815 inches and 2.949 inches -
Pole Quantity
3 -
Arc Quenching Method
Magnetic blowout -
Mounting Facility Type And Quantity
6 threaded hole -
Storage Type
General purpose warehouse -
Thready Qty Per Inch (tpi)
32 -
Maximum Continuous Load Current Rating Per Pole
5.0 amperes ac all locations and 5.0 amperes dc all locations -
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations and 65.0 dc all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations and 1000.0 dc all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Magnetic all locations -
Trip Release Characteristic
Time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
3 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At each pole -
External Actuator Linkage Arrangement
One, two, and three linked -
Auxiliary Switch Function And Quantity
1 alarm -
Internal Trip Release Configuration
Series trip all locations -
Thread Size
0.138 inches -
Switch Location And Position Designation
External at pole three -
Trip Delay Time In Seconds Per Rated Continuous Current
0.210 at 200 pct all locations and 0.800 at 200 pct all locations -
Inclosure Protection Type For Which Designed
Fungus resistant and moisture resistant -
Switch Terminal Type
Turret -
Switch Current Rating And Type In Amps
2.5 ac and 2.0 dc -
Switch Voltage Rating And Type In Volts
240.0 ac and 50.0 dc -
Frequency In Hertz
60.0 all locations -
Test Data Document
01714-g396183 drawing (this is the basic governing drawing, such as a contractor drawing, original equipment manufacturer drawing, etc.; excludes any specification, standard or other document that may be referenced in a basic governing drawing) -
Thread Series Designator
Unc -
Terminal Type And Quantity
6 threaded stud
More from these suppliers
- 5935-00-060-5682 MPN G302678-17Electrical Plug Connector
- 5935-00-150-1677 MPN G396102-5Electrical Receptacle Connector
- 5945-00-622-9906 MPN G302951-5Electromagnetic Relay
- 5985-00-835-0350 MPN 8518996Waveguide Support
- 5925-01-101-3385 MPN G396183AE2R5DP1Circuit Breaker
- 5950-00-024-9964 MPN KS13726L29Radio Frequency Coil
- 5945-00-201-6065 MPN KS5834LIST02Electrical Solenoid
- 5950-00-647-7524 MPN GA51982Power Transformer
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-01-297-3995 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
G396183AG5R0A51 | Lucent Technologies Inc |
G396183AG5R0A51 | Lucent Technologies Inc |
72-309-35MG6 | Eaton Corp |
G396183AG5R0A51 | Eaton Corp |