NSN 5925-01-308-7450
Overload Switch
Multipole-single actuator type body style, plastic case material, moderately rugged fragility factor, pole quantity: 3.
Manufacturer part number 1603AS150 for national stock number 5925013087450.
Datasheet
-
Product description
Circuit Breaker NSN 5925-01-308-7450.
-
MPN or Model
1603AS150
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Unit Weight (Est.)
4.5 lb -
Body Style
Multipole-single actuator type -
Body Length
6.250 inches -
Body Width
4.120 inches -
Body Height
3.315 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
Between 4.850 inches and 4.910 inches -
Center To Center Distance Between Terminals Parallel To Width
Between 1.350 inches and 1.410 inches -
Unthreaded Mounting Hole Diameter
Between 0.182 inches and 0.202 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
3.660 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
Between 1.350 inches and 1.410 inches -
Fragility Factor
Moderately rugged -
Boss Height
0.250 inches -
Pole Quantity
3 -
Mounting Facility Type And Quantity
4 unthreaded hole -
Storage Type
General purpose warehouse -
Special Handling Feature
Magnetic -
Features Provided
Adjustable trip release -
Maximum Continuous Load Current Rating Per Pole
100.0 amperes ac all locations -
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 ac all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Magnetic all locations -
Trip Release Characteristic
Instantaneous all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
1 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At pole two -
Adjustable Trip Setting Current Range Per Pole In Amps
+300.0/+1310.0 ac all locations -
Internal Trip Release Configuration
Series trip all locations -
Inclosure Protection Type For Which Designed
Fungus resistant and moisture resistant -
Frequency In Hertz
60.0 all locations -
Unpackaged Unit Weight
4.680 pounds -
Terminal Type And Quantity
6 compression
More from these suppliers
- 5935-00-007-7336 MPN 247ASC0395-092Electrical Plug Connector
- 5905-00-459-0808 MPN 247AS-C0502-104Film Fixed Resistor
- 5935-00-548-1528 MPN 2641216-29Electrical Plug Connector
- 5975-00-948-3633 MPN 67A30D10Electrical Equipment Mounting Base
- 4820-00-992-6941 MPN 51A137B4Valve Seat
- 4820-01-020-2501 MPN 247ASC2368-001Safety Relief Valve
- 5935-01-046-6336 MPN 917AS1069Plug Dummy Connector
- 5935-01-057-8457 MPN 642AS0507-6Electrical Connector Backshell
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-01-308-7450 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
1603AS150 | Naval Air Systems Command |
TEC36100FP | General Electric Co |