NSN 5925-01-318-3295
Overload Switch
Multipole-single actuator type body style, plastic case material, moderately rugged fragility factor, pole quantity: 3.
Manufacturer part number HMCP030H1 for national stock number 5925013183295.
Datasheet
-
Product description
Circuit Breaker NSN 5925-01-318-3295.
-
MPN or Model
HMCP030H1
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Unit Weight (Est.)
4.5 lb -
Body Style
Multipole-single actuator type -
Body Length
10.000 inches -
Body Width
4.125 inches -
Body Height
4.062 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
9.000 inches -
Center To Center Distance Between Terminals Parallel To Width
1.375 inches -
Unthreaded Mounting Hole Diameter
0.250 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
7.250 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.375 inches -
Fragility Factor
Moderately rugged -
Boss Height
0.250 inches -
Pole Quantity
3 -
Arc Quenching Method
Magnetic blowout -
Mounting Facility Type And Quantity
4 unthreaded hole -
Storage Type
General purpose warehouse -
Special Handling Feature
Magnetic -
Features Provided
Adjustable trip release -
Maximum Continuous Load Current Rating Per Pole
30.0 amperes ac all locations and 30.0 amperes dc all locations -
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations and 250.0 dc all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
25000.0 ac all locations and 10000.0 dc all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Magnetic all locations -
Trip Release Characteristic
Instantaneous all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
1 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At pole two -
Adjustable Trip Setting Current Range Per Pole In Amps
+90.0/+300.0 ac all locations and +90.0/+300.0 dc all locations -
Internal Trip Release Configuration
Series trip all locations -
Inclosure Protection Type For Which Designed
Dustproof -
Frequency In Hertz
50.0 all locations or 60.0 all locations -
Terminal Type And Quantity
6 compression
More from these suppliers
- 5945-00-450-6368 MPN 276A892G01Electromagnetic Relay
- 5950-00-646-1229 MPN 1JH2439PC1EElectrical Coil
- 5945-00-189-0763 MPN 47E5768Electromagnetic Relay
- 5925-00-443-4077 MPN 656D964G04Circuit Breaker
- 5925-00-948-0056 MPN HQP3040HCircuit Breaker
- 5925-01-068-2503 MPN 1279C57G04Circuit Breaker
- 5925-01-242-8723 MPN FC2030Circuit Breaker
- 5925-01-421-2452 MPN 2603D47G26Circuit Breaker Tripper
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
Pricing and Availability
Get a quote for 5925-01-318-3295 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
HMCP030H1 | Eaton Corporation |