1-321-802-5889

NSN 5925-01-377-2041

Overload Switch

About this product

Multipole-single actuator type body style, plastic case material, 2 poles, thready qty per inch (tpi): 32.

Manufacturer part number CD2-A3-DU-0100-02A for national stock number 5925013772041.

Datasheet

  • Product description

    Circuit Breaker NSN 5925-01-377-2041.

  • MPN or Model

    CD2-A3-DU-0100-02A

  • Schedule B
    8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi)
  • NMF (National Motor Freight)
    063160 - Switch Boxes/elec Enclosures
  • Body Style
    Multipole-single actuator type
  • Body Length
    5.125 inches
  • Body Width
    2.075 inches
  • Case Material
    Plastic
  • Center To Center Distance Between Terminals Parallel To Length
    3.547 inches
  • Center To Center Distance Between Terminals Parallel To Width
    3.547 inches
  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
    2.750 inches
  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
    1.026 inches
  • End Application
    Panel a/c 2009-002-01 onboard 47 ft mlb c.G. Vessels
  • Boss Height
    0.219 inches
  • Mounting Surface To Terminal End Distance
    3.485 inches
  • Pole Quantity
    2
  • Mounting Facility Type And Quantity
    6 threaded hole
  • Thready Qty Per Inch (tpi)
    32
  • Maximum Continuous Load Current Rating Per Pole
    100.0 amperes ac all locations
  • Operating Voltage Type And Rating Per Pole In Volts
    240.0 ac all locations
  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
    7500.0 ac all locations
  • Circuit Protection Type
    Overcurrent all locations
  • Trip Release Method
    Magnetic-hydraulic all locations
  • Trip Release Characteristic
    Instantaneous all locations
  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
    135.0 all locations
  • Reset Method
    Manual
  • Main Contact Tripping Mechanism Type
    Trip free
  • Internal Trip Release Configuration
    Series trip all locations
  • Thread Size
    0.138 inches
  • Frequency In Hertz
    50.0 all locations or 60.0 all locations
  • Thread Series Designator
    Unc
  • Terminal Type And Quantity
    2 threaded stud
Circuit Breaker

A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.

Mechanic Bill explains Overload Switch

Pricing and Availability

Get a quote for 5925-01-377-2041 circuit breaker
Quantity:
Your Email:
Your Name:
Company Name:
Optional reference:
Phone:
NSN 5925013772041

We do not share, sell, or distribute your information to any third party.
Privacy | Terms

All major credit cards accepted as well as gov. p-cards
Manufacturer Part Numbers and Alternates
MPN manufacturer part number Registrant or Supplier
CD2-A3-DU-0100-02A Eaton Corp
Stock Check
Availability of this NSN has not been updated recently. Submit the pricing and availbility form above to receive an up to date quote.