NSN 5925-00-892-9932
Overload Switch
Multipole-multiple actuator type body style, plastic case material, moderately rugged fragility factor, pole quantity: 2.
Manufacturer part number 2XAM17-15-208VAC60C56 for national stock number 5925008929932.
Datasheet
-
Product description
Circuit Breaker NSN 5925-00-892-9932.
-
MPN or Model
2XAM17-15-208VAC60C56
-
Schedule B
8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi) -
NMF (National Motor Freight)
061300 - Circuit Breaker/switch NOI -
Unit Weight (Est.)
0.8 lb -
Body Style
Multipole-multiple actuator type -
Bushing Length
Between 0.146 inches and 0.166 inches -
Body Length
Between 2.490 inches and 2.510 inches -
Body Width
Between 1.510 inches and 1.530 inches -
Case Material
Plastic -
Center To Center Distance Between Terminals Parallel To Length
Between 1.180 inches and 1.200 inches -
Center To Center Distance Between Terminals Parallel To Width
Between 0.740 inches and 0.760 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
Between 1.802 inches and 1.822 inches -
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
Between 0.740 inches and 0.760 inches -
Fragility Factor
Moderately rugged -
Mounting Surface To Terminal End Distance
Between 1.990 inches and 2.010 inches -
Pole Quantity
2 -
Arc Quenching Method
Magnetic blowout -
Mounting Facility Type And Quantity
4 threaded hole -
Storage Type
General purpose warehouse -
Thready Qty Per Inch (tpi)
32 -
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac all locations -
Operating Voltage Type And Rating Per Pole In Volts
208.0 ac all locations -
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
3500.0 ac all locations -
Circuit Protection Type
Overcurrent all locations -
Trip Release Method
Magnetic-hydraulic all locations -
Trip Release Characteristic
Time delay all locations -
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations -
Reset Method
Manual -
Main Contact Tripping Mechanism Type
Trip free -
Manual Actuator Type And Quantity
2 toggle -
Actuator Function
Trip-reset -
Actuator Position Designation
At each pole -
External Actuator Linkage Arrangement
One and two linked -
Internal Trip Release Configuration
Series trip all locations -
Thread Size
0.138 inches -
Trip Delay Time In Seconds Per Rated Continuous Current
0.300 at 200 pct all locations and 1.000 at 200 pct all locations -
Inclosure Protection Type For Which Designed
Dustproof and fungus proof -
Frequency In Hertz
60.0 all locations -
Thread Series Designator
Unc -
Terminal Type And Quantity
4 tab w/screw
More from these suppliers
- 5935-00-988-5945 MPN DMS 85040BElectrical Plug Connector
- 5935-01-109-7517 MPN L02764Electrical Plug Connector
- 5950-01-260-2311 MPN 22840072Power Transformer
- 5905-01-268-4271 MPN RC21U1K5JFilm Fixed Resistor
- 5930-01-314-7318 MPN 1579527-6 10001Push Switch
- 5905-01-318-8689 MPN LO4239Inductive Wire Wound Fixed Resistor
- 5935-01-361-6299 MPN 86102-13-A-10Electrical Receptacle Connector
- 4820-01-364-5895 MPN 2612888Ball Valve
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.
![Mechanic Bill explains Overload Switch](/public/images/billy-thinking.png)
Pricing and Availability
Get a quote for 5925-00-892-9932 circuit breakerManufacturer Part Numbers and Alternates
MPN manufacturer part number | Registrant or Supplier |
---|---|
2XAM17-15-208VAC60C56 | Eaton Corp |
C1018-15 | Lockheed Martin Corporation |
DMS 83059B | Dla Land And Maritime |
Stock Check
![](/public/images/partscage_shelf3.png)