NSN 5925-01-026-5114

Overload Switch

About this product

With line and load lugs.

Manufacturer part number TEB122050WL for national stock number 5925010265114.

Datasheet

  • Product description

    Circuit Breaker NSN 5925-01-026-5114.

  • MPN or Model

    TEB122050WL

  • Schedule B
    8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi)
  • Body Style
    Multipole-single actuator type
  • Body Length
    6.3125 inches
  • Body Width
    2.750 inches
  • Body Height
    3.1875 inches
  • Case Material
    Plastic
  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
    4.87501 inches
  • Boss Height
    0.90625 inches
  • Pole Quantity
    2
  • Maximum Continuous Load Current Rating Per Pole
    50.0 amperes dc all locations
  • Operating Voltage Type And Rating Per Pole In Volts
    240.0 ac all locations and 125.0 dc all locations
  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
    10000.0 ac all locations and 5000.0 dc all locations
  • Circuit Protection Type
    Overcurrent all locations
  • Trip Release Method
    Thermal-magnetic all locations
  • Trip Release Characteristic
    Instantaneous all locations and time delay all locations
  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
    125.0 all locations
  • Reset Method
    Manual
  • Main Contact Tripping Mechanism Type
    Trip free
  • Manual Actuator Type And Quantity
    1 toggle
  • Actuator Function
    Reset
  • Trip Delay Time In Seconds Per Rated Continuous Current
    80.000 at 200 pct all locations and 325.000 at 200 pct all locations and 30.000 at 300 pct all locations and 130.000 at 300 pct all locations and 13.000 at 400 pct all locations and 70.000 at 400 pct all locations and 7.000 at 500 pct all locations and 45.000 at 500 pct all locations and 13.000 at 1000 pct all locations and 3.500 at 2000 pct all locations
  • Trip Release Ambient Tempurature Rating
    40.0 degrees celsius all locations
  • Frequency In Hertz
    60.0 all locations
  • Supplementary Features
    Operating voltage type and rating per pole in volts 250.0 dc in addition to cprf
More from these suppliers
Circuit Breaker

A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.

Mechanic Bill explains Overload Switch

Pricing and Availability

Get a quote for 5925-01-026-5114 circuit breaker
Quantity:
Your Email:
Your Name:
Company Name:
Optional reference:
Phone:
NSN 5925010265114

We do not share, sell, or distribute your information to any third party.
Privacy | Terms

All major credit cards accepted as well as gov. p-cards
Manufacturer Part Numbers and Alternates
MPN manufacturer part number Registrant or Supplier
TEB122050WL General Electric Co
Stock Check
Availability of this NSN has not been updated recently. Submit the pricing and availbility form above to receive an up to date quote.