1-321-802-5889

NSN 5925-01-035-3971

Overload Switch

About this product

Multipole-multiple actuator type body style, plastic case material, single pole, double throw switch contact arrangement, fragility factor: moderately rugged.

Manufacturer part number AM3-A2-20-2 for national stock number 5925010353971.

Datasheet

  • Product description

    Circuit Breaker NSN 5925-01-035-3971.

  • MPN or Model

    AM3-A2-20-2

  • Schedule B
    8536.20.0040 (Automatic circuit breakers, for a voltage not exceeding 1, 000 v, nesoi)
  • NMF (National Motor Freight)
    061300 - Circuit Breaker/switch NOI
  • Body Style
    Multipole-multiple actuator type
  • Body Length
    Between 2.490 inches and 2.510 inches
  • Body Width
    Between 2.240 inches and 2.251 inches
  • Case Material
    Plastic
  • Center To Center Distance Between Terminals Parallel To Length
    Between 1.928 inches and 1.948 inches
  • Center To Center Distance Between Terminals Parallel To Width
    Between 0.740 inches and 0.760 inches
  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
    Between 2.052 inches and 2.072 inches
  • Switch Contact Arrangement
    Single pole, double throw
  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
    Between 0.740 inches and 0.760 inches
  • Fragility Factor
    Moderately rugged
  • Boss Height
    Between 0.130 inches and 0.150 inches
  • Mounting Surface To Terminal End Distance
    Between 2.461 inches and 2.481 inches
  • Pole Quantity
    3
  • Arc Quenching Method
    Magnetic blowout
  • Mounting Facility Type And Quantity
    6 threaded hole
  • Storage Type
    General purpose warehouse
  • Thready Qty Per Inch (tpi)
    32
  • Maximum Continuous Load Current Rating Per Pole
    20.0 amperes ac all locations
  • Operating Voltage Type And Rating Per Pole In Volts
    250.0 ac all locations
  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
    1000.0 ac all locations
  • Circuit Protection Type
    Overcurrent all locations
  • Trip Release Method
    Magnetic-hydraulic all locations
  • Trip Release Characteristic
    Time delay all locations
  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
    125.0 all locations
  • Reset Method
    Manual
  • Main Contact Tripping Mechanism Type
    Trip free
  • Manual Actuator Type And Quantity
    3 toggle
  • Actuator Function
    Trip-reset
  • Actuator Position Designation
    At each pole
  • External Actuator Linkage Arrangement
    One, two, and three linked
  • Auxiliary Switch Function And Quantity
    1 alarm
  • Internal Trip Release Configuration
    Series trip all locations
  • Thread Size
    0.138 inches
  • Switch Location And Position Designation
    Internal at pole two
  • Trip Delay Time In Seconds Per Rated Continuous Current
    2.000 at 200 pct all locations and 20.000 at 200 pct all locations
  • Inclosure Protection Type For Which Designed
    Fungus resistant
  • Switch Terminal Type
    Tab, solder lug
  • Switch Current Rating And Type In Amps
    10.0 ac and 4.0 dc
  • Switch Voltage Rating And Type In Volts
    250.0 ac and 30.0 dc
  • Frequency In Hertz
    60.0 all locations
  • Unpackaged Unit Weight
    14.000 ounces
  • Thread Series Designator
    Unc
  • Terminal Type And Quantity
    6 threaded stud
Circuit Breaker

A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see relay (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see relay-switch. Excludes circuit breaker box and magneto "breaker" assemblies. See also switch (as modified); and controller.

Mechanic Bill explains Overload Switch

Pricing and Availability

Get a quote for 5925-01-035-3971 circuit breaker
Quantity:
Your Email:
Your Name:
Company Name:
Optional reference:
Phone:
NSN 5925010353971

We do not share, sell, or distribute your information to any third party.
Privacy | Terms

All major credit cards accepted as well as gov. p-cards
Manufacturer Part Numbers and Alternates
MPN manufacturer part number Registrant or Supplier
AM3-A2-20-2 Eaton Corp